[1]杨 超,杨俊芬,闫西峰,等.750kV 变电构架柱头节点静力性能试验研究[J].西安建筑科技大学学报:自然版,2016,48(02):214-219.[doi:10.15986/j.1006-7930.2016.02.011]
 YANG Chao,YANG Junfen,YAN Xifeng,et al.Experimental study on static behavior top-joint of 750 kV substation truss structures[J].J.Xi’an Univ. of Arch. & Tech.:Natural Science Edition,2016,48(02):214-219.[doi:10.15986/j.1006-7930.2016.02.011]
点击复制

750kV 变电构架柱头节点静力性能试验研究
()
分享到:

西安建筑科技大学学报:自然版[ISSN:1006-7930/CN:61-1295/TU]

卷:
48
期数:
2016年02期
页码:
214-219
栏目:
出版日期:
2016-04-28

文章信息/Info

Title:
Experimental study on static behavior top-joint of 750 kV substation truss structures
文章编号:
1006-7930(2016)02-0214-06
作者:
杨 超1杨俊芬1闫西峰1胡盼盼1张广平2奚增红2
1.西安建筑科技大学土木工程学院, 陕西 西安 710055; 2.甘肃省电力设计院, 甘肃 兰州730050
Author(s):
YANG Chao1 YANG Junfen1 YAN Xifeng1 HU Panpan1 ZHANG Guangping2 XI Zenghong2
1. School of Civil Engineering, Xi’an Univ. of Arch. & Tech., Xi’an 710055, China; 2. Gansu Electric Power Design Institute of State Electric Network, Lanzhou 730050, China
关键词:
钢管混凝土变电构架柱头节点静力试验静力性能
Keywords:
CFT substation structures top-joint static test static behavior
分类号:
TU 398.9
DOI:
10.15986/j.1006-7930.2016.02.011
文献标志码:
A
摘要:
变电构架柱头节点作为一种重要的传力部件将决定整榀构架的安全性,且占用很大一部分用钢量.以国内首例750 kV 钢管混凝土变电构架工程——甘肃桥湾750 kV 变电站为背景,按考虑顶板和剪切板厚度不同的两种构造措施设计了两个1:2 缩尺节点,并对其进行了单调静力试验.试验结果表明,两种节点均能满足工程要求,且有较高的安全储备和延性,节点最终破坏模式均为非节点区杆件破坏,而节点区各板件应力水平尚处于弹性状态、内填混凝土完好,符合“强节点弱杆件”的设计原则.
Abstract:
The top-joint of herringbone truss-column is a key force transmission component which affects the safety of the whole structure, and it will take a large amount of steel  consumption simultaneously. Based on the engineering background of the first CFT 750 kV substation named Qiaowan substation in China’s Gansu province, two different constructional details of 1:2 scale CFT top-joint specimens, one with more thick shear plate and the other more thick top plate respectively, were designed and applied on the monotonic static test. Test results indicate that the two kinds of top-joints can meet the engineering requirement, and have sufficient safety reserves and ductility. The failure pattern of two joints are non-joint region failure, while each plate at the joint region is still in elastic stress level and the filled concrete is flawless, in accordance with the design concept of ’strong-joint and weak-member.

参考文献/References:

[1] 陈传新, 刘素丽. 750 kV 变电构架结构选型[J].电力建设, 2007, 28(5): 33-35.

CHEN Chuanxin, LIU Suli. Selection of 750 kV substation truss structures [J]. Electric Power Construction, 2007, 28 (5): 33-35.

[2] 韩林海. 钢管混凝土结构-理论与实践[M]. 北京: 科学出版社, 2007.

HAN Linhai. Concrete filled steel tubular structure theory and practice[M]. Beijing: Science Press, 2007.

[3] 高赞. 750 kV 变电构架结构型式优化研究[D]. 兰州:兰州大学, 2013.

GAO Zan. Research of optimization on types of 750 kv substation truss structures [D]. Lanzhou: Lanzhou University,2013.

[4] 甘肃省电力设计院, 兰州大学. 变电构架结构优化设计研究[R]. 兰州: 兰州大学, 2012.

Gansu Electric Power Design Institute of Sate Electric Network, Lanzhou University. Research of optimization on types substation truss structures[R]. Lanzhou: Lanzhou University, 2012.

[5] 变电站建筑结构设计规程: DLT 5457-2012 [S]. 北京:中国计划出版社, 2012.

Technical code for the design og substation building and structures: DLT 5457-2012 [S]. Beijing: China Planning Press, 2012.

[6] 中南电力设计研究院. 变电构架设计手册[M].武汉:湖北科学技术出版社, 2006.

Central Southern China Electric Power Design Institute. Design manual for structure gantry of switchyard[M].Wuhan: Hubei Science and Technology Press, 2006.

[7] 朱爱珠, 郭耀杰, 程超, 等. 变电构架柱的节点试验研究与有限元分析[J]. 土木工程学报, 2007, 40(11): 9-14.

ZHU Aizhu, GUO Yaojie, CHENG Chao et al. Experimental study and finite element analysis on the joint of power transformation truss-column[J]. China Civil Engineering Journal, 2007, 40(11): 9-14.

[8] 卢海路. 变电构架高架柱与人字柱连接节点受力性能试验研究[D]. 西安: 西安建筑科技大学, 2011.

LU Hailu. Experiment on the mechanic behavior of joint between A-column and evevated column in substation frame[D]. Xi’an: Xi’an Univ. of Arch. & Tech., 2011.

[9] 刘广鹏. 变电构架中高架柱与人字柱连接节点受力性能有限元分析[D]. 西安: 西安建筑科技大学, 2011.

LIU Guangpeng. Finite element analysis on mechanical properties of joints between elevated columns and A-columns[D]. Xi’an: Xi’an Univ. of Arch. & Tech., 2011.

[10] HUANG Chao, HAN Xiaolei, JI Jing, et al. Behavior of concrete filled steel tubular planar intersecting connections under axial compression, Part 1: Experimental study[J]. Engineering Sructures, 2010, 32(1): 60-68.

[11] KOSTESKI N, PACKER J A, PUTHLI R S. A finite element method based yield load determination procedure for hollow structural section connections [J]. Journal of Constructional Steel Research, 2003, 59(4): 453-471.

[12] 章为民, 陆明万, 张如一. 确定实际极限载荷的零曲率准则[J]. 固体力学学报, 1989(2): 152-160.

ZHANG Weimin, LU Mingwan, ZHANG Ruyi. A zero curvecrit erion to determine the practicalcoll apse load [J].Acta Mechanics Solida Sinica, 1989(2): 152-160.

[13] WANG Y Q, ZONG L, SHI Y J. Bending behavior and design model of bolted flange-plate connection[J]. Journal of Constructional Steel Research, 2013(84): 1-16.

备注/Memo

备注/Memo:
收稿日期:2015-07-15 修改稿日期:2016-01-26
基金项目:住房和城乡建设部2014 年科学技术基金资助项目(2014-K2-011);陕西省自然科学基础研究基金资助项目(2014JM7244);国家电网公司2014年依托工程基建新技术研究项目
作者简介:杨超(1987-),男,博士生,主要从事钢结构稳定与抗震方面研究. E-mail: cymyc@foxmail.com
更新日期/Last Update: 2016-05-22