[1]王占伟,王智伟,闫增峰.某地下水源热泵系统制热工况测试分析与运行优化[J].西安建筑科技大学学报(自然科学版),2017,49(01):125-130.[doi:10.15986/j.1006-7930.2017.01.020]
 WANG Zhanwei,WANG Zhiwei,YAN Zengfeng.Testing analysis and operation optimization of the heating mode of a ground water source heat pump system[J].J. Xi’an Univ. of Arch. & Tech.(Natural Science Edition),2017,49(01):125-130.[doi:10.15986/j.1006-7930.2017.01.020]
点击复制

某地下水源热泵系统制热工况测试分析与运行优化()
分享到:

西安建筑科技大学学报(自然科学版)[ISSN:1006-7930/CN:61-1295/TU]

卷:
49
期数:
2017年01期
页码:
125-130
栏目:
出版日期:
2017-03-03

文章信息/Info

Title:
Testing analysis and operation optimization of the heating mode of a ground water source heat pump system
文章编号:
1006-7930(2017)01-0125-06
作者:
王占伟1王智伟1闫增峰2
(西安建筑科技大学环境与市政工程学院,陕西 西安 710055 ;2. 西安建筑科技大学建筑学院,陕西 西安 710055 )
Author(s):
WANG Zhanwei1 WANG Zhiwei 1 YAN Zengfeng2
(1. School of Environment, Xian Univ. of Arch. & Tech., Xian 710055, China ; 2. School of Arch., Xian Univ. of Arch. & Tech., Xian 710055, China)
关键词:
地下水源热泵 制热工况 测试 能效 运行优化
Keywords:
ground water source heat pump heating condition measurement energy efficiency optimizing operation
分类号:
TUB831
DOI:
10.15986/j.1006-7930.2017.01.020
文献标志码:
A
摘要:
对某住宅小区的地下水源热泵系统进行了连续三个冬季的运行监测.监测结果显示,地下水源热泵系统有着较高的供暖能效,但系统运行较长时间后能效会出现下降.通过对监测数据的分析,获得了机组容量、相同机组容量下的两台压缩机的不同容量组合和负荷侧进机组的水温对机组能效的影响规律,并提出了针对这三因素的优化运行策略.
Abstract:
The operational conditions of a residential ground water source heat pump (GWHP) system operating in three successive winters in Hanzhong were tested. Results show that the GWHP system has high heating energy efficiency, but its energy efficiency will decrease after it has been in operation for a long time. According to the analysis of the testing data, the laws affecting the capacity of unit, the combinations of different capacities of double compressors in condition of the same capacity of unit and the inlet temperature of condenser affect ing the energy efficiency of unit are obtained. Meanwhile, the strategies of optimizing operation about these three factors are proposed.

参考文献/References:

[1] International energy agency. World Energy Outlook (2012) [M]. Paris: Organization for Economic Co-operation and Development (OECD), 2012.

[2] 清华大学建筑节能研究中心. 中国建筑节能年度发展研究报告(2015)[R].北京:中国建筑工业出版社, 2015.

Building Energy Conservation Research Center, Tsinghua University. Annual report on china building energy efficiency(2015)[R]. Beijing: China Building Industry Press,2015.

[3] Zhang S, Zhang L, Wei H, et al. Field testing and performance analyses of ground source heat pump systems for residential applications in Hot Summer and Cold Winter area in China[J]. Energy and Buildings, 2016, 133: 615-627.

[4] Zhai X Q, Cheng X W, Wang R Z. Heating and cooling performance of a minitype ground source heat pump sys- tem[J]. Applied Thermal Engineering, 2017, 111: 1366-1370.

[5] 龚光彩, 张翔翼, 陆凌, 等. 水源热泵系统设计冬季参考水温确定方法的探讨[J]. 建筑科学,2016, 32(4): 128-133.

GONG Guangcai, ZHANG Xiangyi, LU Ling, et al. Discussion on Method of Designed Reference Water Temperature in Winter for Water Source Heat Pump System[J]. Building Science, 2016, 32(4): 128-133.

[6] 陈阳,王智伟,刘炜,等. 地下水源热泵热源井设计及施工关键问题研究[J]. 建筑科学, 2016, 32(4): 87-92.

CHEN Yang, WANG Zhiwei, LIU Wei, et al. Study of key problems of design and construction for heat source well of groundwater heat pump[J]. Building Science, 2016, 32(4): 87-92.

[7] 舒海文,祝明睿,曾琦杰,等. 大连某海水源热泵区域供热系统的实测分析[J]. 暖通空调, 2014, 44(11): 62-66.

SHU Haiwen, ZHU Mingrui, ZENG Qijie, et al. Field measurement and analysis of a seawater source heat pump district heating system in Dalian[J]. HV&AC, 2014, 44(11): 62-66.

[8] 李峥嵘,傅强,钱必华,等. 上海某办公楼土壤源热泵系统冬季运行特性实测分析[J]. 西安建筑科技大学学报(自然科学版),2015,47(3):413-417.

LI Zhengrong, FU Qiang, QIAN Bihua, et al. Winter performance analysis for a ground-coupled heat pump system of an office building in Shanghai[J]. J. Xi’an Univ. of Arch. & Tech.(Natural Science Edition), 2015,47(3):413-417.

[9] 雷飞,胡平放,黄素逸,等. 地下水源热泵空调系统的实测以及能效火用分析[J]. 流体机械,2012,40(2): 57-62.

LEI Fei, HU Pingfang, HUANG Suyi, et al. Energy and Exergy Analysis of A Ground Water Heat Pump System[J]. FLUID MACHINERY, 2012, 40(2): 57-62.

[10] 陈焰华,於仲义,胡平放,等. 武汉地区地源热泵系统的运行测试与分析[J]. 暖通空调,2009,39(6):12-17.

CHEN Yanhua, YU Zhongyi, HU Pingfang, et al. Operation Testing and Analysis of Ground-Source Heat Pump Systems in Wuhan Area[J]. HV&AC, 2009, 39(6):12-17.

[11] 中华人民共和国建设部. 地源热泵系统工程技术规范:GB/T50366-2009[S]. 北京:中国建筑工业出版社,2009.

Ministry of Construction of the P. R. C. GB/T50366-2009. Technical code for ground-source heat pump system[S]. Beijing: China Building Industry Press, 2009.

[12] WANG Zhanwei, WANG Zhiwei, YAN Zengfeng. The Method of Field Date Collection and Date Validity For Energy Efficiency Diagnosis in Heat Pump Operating. [J]. Lecture Notes in Electrical Engineering, 2014, 263:593-601.

[13] WANG Zhiwei, WANG Zhanwei, YAN Zengfeng. A Fault Diagnosis Model and its Application in Chiller Operating. [J]. Applied Mechanics & Materials, 2013, 294:1851-1856.

备注/Memo

备注/Memo:
基金项目:“十二五”国家科技支撑计划项目“夏热冬冷地区供暖模式与相关装备的研发及示范”(2011BAJ03B06)
收稿日期:2014-12-04 修改稿日期:2017-01-03
作者简介:王占伟(1987-),男,博士研究生,主要研究空调系统能效诊断理论与节能技术.E-mail: wzhanweisunshine@163.com
更新日期/Last Update: 2017-03-16