[1]孟庆龙,王文强,郭雪丽,等.变流量空调水系统稳定性的定量评价[J].西安建筑科技大学学报(自然科学版),2019,51(03):432-439,446.[doi:10.15986/j.1006-7930.2019.03.019]
 MENG Qinglong,WANG Wenqiang,GUO Xueli,et al.Quantitative evaluationon stability of variable water volume air-conditioning system[J].J. Xi’an Univ. of Arch. & Tech.(Natural Science Edition),2019,51(03):432-439,446.[doi:10.15986/j.1006-7930.2019.03.019]
点击复制

变流量空调水系统稳定性的定量评价()
分享到:

西安建筑科技大学学报(自然科学版)[ISSN:1006-7930/CN:61-1295/TU]

卷:
51
期数:
2019年03期
页码:
432-439,446
栏目:
出版日期:
2019-06-30

文章信息/Info

Title:
Quantitative evaluationon stability of variable water volume air-conditioning system
文章编号:
1006-7930(2019)03-0432-08
作者:
孟庆龙12王文强1郭雪丽2常赛南2谷雅秀1
(1. 长安大学 建筑工程学院,陕西 西安 710061;2. 长安大学 环境科学与工程学院,陕西 西安 710054)
Author(s):
MENG Qinglong2 WANG Wenqiang1 GUO Xueli2 CHANG Sainan2 GU Yaxiu1
(1. School of Civil Engineering; Chang′an University, Xi′an 710061, China; 2 School of Environmental Science and Engineering, Chang′an University, Xi′an 710054, China.)
关键词:
空调水系统水力稳定性压差控制TRNSYS节能
Keywords:
air-conditioning system hydraulic stability differential pressure controlTRNSYS energy saving
分类号:
TU831.3
DOI:
10.15986/j.1006-7930.2019.03.019
文献标志码:
A
摘要:
以一次泵变流量水系统为研究对象,实验研究了无压差控制和定压差控制下变流量空调水系统的水力稳定性.建立了相应的TRNSYS仿真模型,仿真研究了变压差控制下水系统的水力稳定性.结果表明:对于提高系统水力稳定性和节能效益,变压差控制策略效果显著.变压差控制下管网的水力失调系数为0.072,较无压差控制时减小了0.442;关闭任一支路阀门,变压差控制下冷冻水泵节能可达到27.1%.
Abstract:
Taking the primary variable displacement water system as the research object, the hydraulic stability of the variable flow air conditioning system under none-pressure control and constant pressure difference control was experimentally studied. The corresponding TRNSYS simulation model was established and the hydraulic stability of the water system under variable pressure difference control was simulated. The results show that the effect of variable pressure differential control strategy is significant for improving the hydraulic stability and energy saving efficiency of the system. The hydraulic imbalance coefficient of the pipe network under variable pressure difference control is 0.072, which is 0.442 when compared with no pressure difference control. When the valve of any branch is closed, the energy saving of the frozen water pump under variable pressure difference control can reach 27.1%.

参考文献/References:

[1]李晓鹏,黄志浪,曹迪华.暖通空调系统中的水力平衡[J] .空调暖通技术, 2006(1): 14-16.

LI Xiaopeng, HUANG Zhilang, CAO Dihua. Hydraulic balance of HVAC systems [J]. Technology of HV&AC, 2006(1): 14-16.
[2]KIRSNER W. Troubleshooting: Chilled water distribution problems at the NASA Johnson Space Center [J]. Heating Piping & Air Conditioning, 1995, 67(2): 489-501.
[3]KIRSNER W. Chilled water plant design [J]. Heating Piping & Air Conditioning, 1996, 68(1): 73-80.
[4]董宝春, 刘传聚, 刘东, 等.一次泵/二次泵变流量系统能耗分析[J].暖通空调, 2005, 35(7): 82-85.
DONG Baochun, LIU Chuangju, LIU Dong, et al. Energy consumption analysis of primary pump and primary secondary pump systems with variable flow rate [J]. HV & AC, 2005, 35(7): 82-85.
[5]江亿.管网可调性和稳定性的定量分析[J].暖通空调,1997, 27(3): 5-7.
JIANG Yi. Adjustability and stability of hydraulic networks [J]. HV&AC, 1997, 27(3): 5-7.
[6]秦绪忠,江亿.供热空调水系统的稳定性分析[J].暖通空调, 2002, 32(1): 13-14.
QIN Xuzhong, JIANG Yi. Stability analysis of hydraulic networks in heating and air conditioning systems [J]. HV&AC, 2002, 32(1): 13-14.
[7]LIU Xuefeng, LIU J, CHEN X, et al. Static stability analysis of air-conditioning chilled water system for variable differential pressure control considering bypass loop regulation characteristics[J]. Journal of Shanghai Jiaotong University, 2014, 48(6): 772-777.
[8]LIU Xuefeng, LIU J, LU J, et al. Research on operating characteristics of direct-return chilled water system controlled by variable temperature difference [J]. Energy, 2012, 40(1): 236-249.
[9]MOORE B.J., FISHER D.S. Pump pressure differential set-point reset based on chilled water valve position [J]. ASHRAE Transactions. 2003, 109(1):371-377.
[10]李彬,肖勇全,马秀力.变流量空调水系统稳定性的分析及试验研究[J].制冷与空调,2005,19(1): 7-12.
LI Bin, XIAO Yongquan, MA Xiuli. Stability analysis of air conditioning water system in variable water volume system and experimental investigation [J]. Refrigeration & Air-condition, 2005, 19(1): 7-12.
[11]张再鹏,陈焰华,符永正.压差控制对变流量空调水系统水力稳定性的影响[J].暖通空调, 2009,39(6): 63-66.
ZHANG Zaipeng, CHEN Yanhua, FU Yongzheng. Effect of pressure difference control on hydraulic stability of variable flow air conditioning water systems [J]. HV&AC, 2009, 39(6): 63-66.
[12]BYNUM Harris, MERWIN Ed. Variable flow-a control engineer’s perspective [J]. ASHRAE Journal, 1999, 41(1): 26-30.
[13]ZHAO Tianyi,ZHANG Jili,SUN D. Experimental analysis of the thermal stability of the pressure control method for a variable flow air-conditioning water system [J]. Building and Environment. 2013, 70(12): 1-9.
[14]QIANG J, GUO J, SUI Z. Study on the pressure difference control in variable flow rate central heating systems [J]. Applied Mechanics & Materials, 2012, 193-194: 1239-1242.
[15]WU X, YANG C, WU D, et al. Energy saving analysis of pressure difference control of frequency conversion variable water flow system [J]. Proceedings Building Simulation, 2007, 1-3: 624-628.
[16]迟光亮, 张吉礼.基于TRNSYS的空调水系统管网模型的建立[J].建筑热能通风空调, 2011, 30(04): 6-10.
CHI Guangliang, ZHANG Jili. Establishment of pipe network model in air Conditioning water system based on TRNSYS [J]. Building Energy & Environment, 2011, 30(04): 6-10.
[17]季科, 张永贵, 刘冰冰,等.基于TRNSYS的空调水系统仿真平台[J].暖通空调, 2015, 45(05): 93-96.
JI Ke, ZHANG Yonggui, LIU Bingbing, et.al. Simulation platform of air conditioning water system based on TRNSYS [J]. HV&AC, 2015, 45(05): 93-96.
[18]林兴斌, 潘毅群, 黄治钟.变风量空调系统不同控制策略下的能耗分析[J] .建筑热能通风空调, 2010, 29(5):20-24.
LIN Xingbin, PAN Yiqun, HUANG Zhizhong. Analyses of the Energy Performance of VAV System with Different Control Strategies [J]. Building Energy & Environment, 2010, 29(5): 20-24.
[19]赵天怡, 张吉礼, 孙德兴.变流量空调水系统热力稳定性动态分析[J].天津大学学报, 2009, 42(9): 833-838.
ZHAO Tianyi, ZHANG Jili, SUN Dexing. Dynamic analysis of thermodynamic stability in variable water flow HVAC system [J]. Journal of Tianjin University, 2009, 42(9): 833-838.

备注/Memo

备注/Memo:
收稿日期:2018-07-08修改稿日期:2019-05-26
基金项目:国家自然科学基金(51208059); 陕西省自然科学基础研究计划自然科学基金(2018JM5084); 长安大学中央高校基本科研业务费专项资金资助(300102289103)
第一作者:孟庆龙(1979-),男,博士,副教授,硕士生导师,主要从事建筑节能的研究.E-mail:mengqinglong@chd.edu.cn
更新日期/Last Update: 2019-07-22