[1]包继虎,曹 晨,石竹青,等.基于JB/T 9066—1999《柜式风机盘管机组》热工性能测试分析[J].西安建筑科技大学学报(自然科学版),2023,55(03):468-474.[doi:10.15986/j.1006-7930.2023.03.019 ]
 BAO Jihu,CAO Chen,SHI Zhuqing,et al.Analysis of thermal performance test based on JB/T 9066—1999 cabinet type fan coil unit[J].J. Xi'an Univ. of Arch. & Tech.(Natural Science Edition),2023,55(03):468-474.[doi:10.15986/j.1006-7930.2023.03.019 ]
点击复制

基于JB/T 9066—1999《柜式风机盘管机组》热工性能测试分析()
分享到:

西安建筑科技大学学报(自然科学版)[ISSN:1006-7930/CN:61-1295/TU]

卷:
55
期数:
2023年03期
页码:
468-474
栏目:
出版日期:
2023-06-28

文章信息/Info

Title:
Analysis of thermal performance test based on JB/T 9066—1999 cabinet type fan coil unit
文章编号:
1006-7930(2023)03-0468-07
作者:
包继虎曹 晨石竹青陆婷婷马金平李宏哲杨 弋
(合肥通用机械研究院有限公司,安徽 合肥 230031)
Author(s):
BAO Jihu CAO Chen SHI Zhuqing LU Tingting MA Jinping LI Hongzhe YANG Yi
(Hefei General Machinery Research Institute Co. Ltd., Hefei 230031, China)
关键词:
柜式风机盘管机组 热工性能试验 分析 热力学第一定律
Keywords:
cabinet type fan coil unit thermal performance test analysis first law of thermodynamics
分类号:
TU111.3
DOI:
10.15986/j.1006-7930.2023.03.019
文献标志码:
A
摘要:
基于JB/T 9066—1999《柜式风机盘管机组》附录A给出的热工性能试验方法,对柜式风机盘管机组的水侧系统和空气侧系统热工性能试验方法进行了详细解读,根据热力学第一定律,分析了柜式风机盘管机组的水侧和空气侧热平衡性理论,结果显示:水侧的供冷(热)量与热量平衡侧的供冷(热)量存在本质区别.最后归纳了柜式风机盘管机组热工性能试验需要注意的一些事项:在保证标准静压的情况下对柜式风机盘管的热工性能进行试验,相应地,热工性能试验时所测风量是指标准空气状态下的风量,在柜式风机盘管机组供热性能试验时,其水流量等于供冷性能试验时确定的流量.
Abstract:
Based on the thermal performance test method given in appendix A of JB/T9066-1999 “Cabinet type fan coil unit”, the thermal performance test method of water side and air side systems of the cabinet type fan coil unit are interpreted in detail. According to the first law of thermodynamics, the heat balance theory of water side and air side of the cabinet type fan coil unit is analyzed. The results show that the cooling(heating)capacity of the water system is essentially different from that of the thermal equilibrium side. Finally, some precautions for thermal performance testing of cabinet type fan coil units are summarized: the thermal performance of cabinet type fan coil units is tested while ensuring standard static pressure, and correspondingly, the measured air volume during the thermal performance test refers to the air volume under standard air conditions. In the heating performance test of cabinet type fan coil units, the water flow rate is equal to the flow rate determined during the cooling performance test.

参考文献/References:

[1]刘孝刚. 对全空气中央空调系统运行管理的研究[J]. 黑龙江科技信息, 2014, 30: 96.
LIU Xiaogang. Research on operation management of all-air central air-conditioning system[J]. Heilongjiang science and Technology Information, 2014, 30: 96.
[2]李炎锋, 张宁, 边江. 风机盘管空调系统智能控制方案的实验研究[J]. 西安建筑科技大学学报(自然科学版), 2014, 46(5): 731-736.
LI Yanfeng, ZHANG Ning, BIAN Jiang. Experimental research on intelligence control scheme for fan coil air-conditioning system[J]. J. Xi'an Univ. of Arch. & Tech.(Natural Science Edition), 2014, 46(5): 731-736.
[3]王曙光, 赵成刚. 特殊工况下风机盘管、柜式空调箱的选型计算[J]. 低温与特气, 2002, 20(5): 15-18.
WANG Shuguang, ZHAO Chenggang. Type selections and calculation of fan coil system and chest-type air-conditioning case[J]. Low Temperature and Specialty Cases, 2002, 20(5): 15-18.
[4]JOSE' Ferna'ndez-Seara, RUBE'n Diz, FRANCISCO J Uh'a, et al. Experimental analysis on pressure drop and heat transfer of a terminal fan-coil unit with ice slurry as cooling medium[J]. International Journal of Refrigeration, 2010, 33: 1095-1104.
[5]程昆. 空气处理机组的仿真与应用研究[D]. 西安: 西安建筑科技大学, 2006.
CHENG Kun. Research of simulation and faults diagnosis of the air-handle units[D]. Xi'an: Xi'an Univ. of Arch. & Tech., 2006.
[6]AKSHAY Ranade, GREGORY Provan, ALIE El-Din Mady, et al. A computationally efficient method for fault diagnosis of fan-coil unit terminals in building heating ventilation and air conditioning systems[J]. Journal of Building Engineering, 2020, 27: 1-13.
[7]LI Xiuming, ZHAO Tianyi, ZHANG Jili, et al. Development of network control platform for energy saving of fan coil units[J]. Journal of Building Engineering, 2017, 12: 155-160.
[8]YE Jiayu, LIU Xinyi, XU Laifu, et al. Experimental study on the heating and humidifying performance of fan coil units with humidification modules in severe cold regions[J]. Energy & Building, 2022, 276: 1-15.
[9]王智伟, 闰清, 闫增峰. 基于流量冷量关系模型的冷计量方法研究[J]. 西安建筑科技大学学报(自然科学版), 2015, 47(2): 276-281.
WANG Zhiwei, YAN Qing, YAN Zengfeng. Study on the method for cooling metering based on the model of relationship between flow and cooling[J]. J. Xi'an Univ. of Arch. & Tech.(Natural Science Edition), 2015, 47(2): 276-281.
[10]LAURE F, MORETTI F, COPAZZOLI A, et al. Building fan coil electric consumption analysis with fuzzy approaches for fault detection and diagnosis[J]. Energy Procedia, 2014, 62: 411-420.
[11]王磊. 带热回收的空气处理机组模型分析[D]. 上海: 上海交通大学, 2016.
WANG Lei. Modeling analysis of AHU with heat recovery[D]. Shanghai: Shanghai Jiaotong University, 2016.
[12]ANITA Martincˇevic', MARIO Vaak, VINKO Leic'. Identification of a control-oriented energy model for a system of fan coil units[J]. Control Engineering Practice, 2019, 91: 1-11.
[13]国家机械工业局. 柜式风机盘管机组: JB/T 9066—1999[S]. 北京: 机械工业部机械标准化研究所出版.
State Bureau of Machine Building Industry. Cabinet type fan coil unit: JB/T 9066—1999[S]. Beijing: China Standards Press.
[14]包继虎, 曹晨, 丁辉, 等. 基于焓值法的风机盘管机组热工性能分析[J]. 建筑节能, 2022, 50(381): 123-128.
BAO Jihu, CAO Chen, DING Hui, et al. Thermal performance analysis of fan coil unit based on enthalpy method[J]. Journal of BEE, 2022, 50(381): 123-128.
[15]包继虎, 李亚运, 付炜, 等. 空气冷却器与空气加热器性能测试解析[J]. 流体机械, 2022, 50(10): 70-75.
BAO Jihu, LI Yayun, FU Wei, et al. Analysis on performance test methods of the air cooler and air heater[J]. Fluid Machinery, 2022, 50(10): 70-75.
[16]邱信立, 廉乐明, 李力能. 工程热力学[M]. 北京: 中国建筑工业出版社, 1995.
QIU Xinli, LIAN Leming, LI Lineng. Engineering thermodynamics[M]. Beijing: China Architecture & Building Press, 1995.
[17]朱达升. 干空气与湿空气流量的换算方法[J]. 石油化工设备, 1992, 21(4): 21, 47.
ZHU Dasheng. Conversion method of dry air flow and wet air flow[J]. Petro-Chemical Equipment, 1992, 21(4): 21, 47.
[18]田忠保. 空气调节[M]. 西安: 西安交通大学出版社, 1994:4-9.
TIAN Zhongbao. Air conditioning[M]. Xi'an: Xi'an Jiaotong University Press, 1994:4-9.
[19]中华人民共和国国家质量监督检验检疫总局. 组合式空调机组: GB/T 14294—2008[S]. 北京: 中国标准出版社,2009.
General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China. Central-station air handling units: GB/T 14294—2008[S]. Beijing: China Standards Press,2009.
[20]国家市场监督管理总局. 风机盘管机组: GB/T 19232—2019[S]. 北京: 中国标准出版社,2020.
State administration for Market Regulation. Fan coil unit: GB/T 19232—2019[S]. Beijing: China Standards Press,2020.
[21]国家机械工业委员会. 采暖通风与空气调节设备噪声声功率级的测定工程法: GB 9068—1988[S]. 北京: 中国标准出版社,1989.
State Commission of Machinery Industry. Determination of sound power levels for noise emitted by heating-ventilating and air conditioning equipment-engineering method: GB 9068—1988[S]. Beijing: China Standards Press,1989.

备注/Memo

备注/Memo:
收稿日期:2022-02-16修回日期:2023-05-11
基金项目:安徽省市场监督管理局项目(2022011977); 国家重点研发计划基金项目(2020YFF0218600)
第一作者:包继虎(1977—),男,博士,高级工程师.主要从事制冷空调产品检测技术方向的研究.E-mail:tiger0203@163.com
更新日期/Last Update: 2023-06-28