[1]张建锋,张栋喆,周 超,等.滤层配置特征对砂滤池过滤性能的影响[J].西安建筑科技大学学报:自然科学版,2014,46(05):737-741.[doi:10.15986/j.1006-7930.2004.05.021]
 ZHANG Jianfeng,ZHANG Dongzhe,ZHOU Chao,et al..Effect of filter media configuration characteristics on the performance efficiency in quartz sand filter[J].J.Xi’an Univ. of Arch. & Tech.:Natural Science Edition,2014,46(05):737-741.[doi:10.15986/j.1006-7930.2004.05.021]
点击复制

滤层配置特征对砂滤池过滤性能的影响()
分享到:

西安建筑科技大学学报:自然科学版[ISSN:1006-7930/CN:61-1295/TU]

卷:
46
期数:
2014年05期
页码:
737-741
栏目:
出版日期:
2014-10-31

文章信息/Info

Title:
.Effect of filter media configuration characteristics on the performance efficiency in quartz sand filter
文章编号:
1006-7930(2014)05-0737-05
作者:
张建锋1张栋喆1周 超1王小亻毛 2杨宏伟2解跃峰2
(1.西安建筑科技大学环境与市政工程学院,陕西 西安 710055 ; 2.清华大学环境学院环境模拟与污染控制国家重点联合实验室,北京 100084 )
Author(s):
ZHANG Jianfeng1 ZHANG Dongzhe 1 ZHOU Chao 1 WANG Xiaomao 2 YANG Hongwei2 XIE Yuefeng 2
(1. School of Environment and Municipal Engineering, Xi’an Univ. of Arch. & Tech., Xi’an 710055, China; 2. State Key Joint Laboratory of Environmental Simulation and Pollution Control, School of Environment, Tsinghua University , Beijing 100084, China)
关键词:
滤层构造特征过滤性能颗粒物截留
Keywords:
filter media configuration filtration performance particles count control
分类号:
TU991.24
DOI:
10.15986/j.1006-7930.2004.05.021
文献标志码:
A
摘要:
滤料粒径、层厚和颗粒分布等滤层配置特征,是保证滤池高效运行的关键因素之一.根据实际应用构造了三种典型的模拟滤层,进行系统的过滤对比试验,研究滤层构造特征对过滤性能的影响.试验结果表明,均质滤料滤层在水头损失增长率、滤后水平均浊度、颗粒物截留效果、滤层产水率以及过滤性能指标F值等多个方面具有优势;滤后水颗粒物截留效果主要决定于滤层厚度,与滤层厚径比L/d值没有相关性;砂滤层对于水中2~5 μm之间的颗粒物截留效果差;“细粒径、浅滤层”的滤层配置尽管避免了过滤末期浊度值的上升,但存在水头损失增长率大、滤后水平均浊度高、残留颗粒总数大等弊端,采用“深滤层、均质滤料”的滤层配置方式应是今后水厂滤池设计和技术改造的主要技术措施.
Abstract:
The particle size, bed depth and configuration of filter media play a key role in filtration process. Based on the practice, three typical monomedium sand configurations were selected to conduct performance comparison with several focuses. The results revealed that homogeneous sand media have some advantages in head-loss increasing control, filtered water average turbidity, part icles removal efficiency, filter net production ratio and performance index F value. The particle count control depended on the bed depth mainly, and the effect of filter media equivalent depth L/d on particle removal was proved. The particles with size 2~5 μm was the most groups difficult to remove with sand filter. The less size and depth of media configuration means higher head loss increasing, higher filtered water turbidity and particles count, although this configuration could avoid the detrimental effect from turbidity increasing at the end of run. All of above, the media configuration with deeper bed depth and more uniform size distribution along depth should be regarded as the prior alternative choice for filter design and prompting in the future.

参考文献/References:

参考文献 References
[1] 朱洁, 陈洪斌, 孙博雅. 颗粒物计数法用于给水处理的评述[J]. 净水技术, 2009, 28(1):1-6.
ZHU Jie, CHEN Hongbin, SUN Boya. Application of particles counting in water treatment[J]. Water Purification Technology,
2009, 28(1):1-6.
[2] CLEASBY John L, LOGSDON Gary S. Granular bed and precoat filtration. In: AWWA. water quality and treatment—a handbook
of community water supplies[M]. 5th ed. New York: Mc Graw Hill, 2000.
[3] 杨艳玲, 李星, 丛丽, 等. 优化监测与净水工艺提高致病原生动物去除率[J]. 给水排水, 2003, 29(6):22-26.
YANG Yanling, LI Xing, CONG Li, et al. Optimizing of water quality monitoring and removal of pathogenic protozoa in waterworks[
J]. Water & Wastewater Engineering, 2003, 29(6):22-26.
[4] 周超, 张建锋, 何华, 等. 砂滤池对水中颗粒物截留效果及反冲洗效果的分析[J]. 给水排水, 2013, 39(9):24-29.
ZHOU Chao, ZHANG Jianfeng, He Hua, et al. Analysis on the effects of retaining particles and back-washing in sand filter[J].
Water & Wastewater Engineering, 2013, 39(9):24-29.
[5] 王利平, 张世华, 王峰慧, 等. 均质石英砂滤料过滤性能的试验研究[J]. 西安建筑科技大学学报: 自然科学版, 1996,
28(1):65-69.
WANG Liping, ZHANG Shihua, WANG Fenghui, et al. Study on the performance of filtration by uniform quartz san media[J].
J. Xi’an Univ. of Arch. & Tech.: Natural Science Edition, 1996, 28(1):65-69.
[6] 张建锋, 王磊波. 滤池气水反冲洗强度控制指标的建立与分析[J]. 给水排水, 2008, 34(2):15-18.
ZHANG Jianfeng, WANG Leibo. Establishment and analysis of strength index for air scour and water backwash of filter[J].
Water & Wastewater Engineering, 2008, 34(2):15-18.
[7] 许保玖. 给水处理理论[M]. 北京:中国建筑工业出版社, 2000.
XU Baojiu. Water treatment theories and principles[M]. Beijing: China Architecture & Building Press, 2000.
[8] HSU Bingmu, YEH Hsuan-hsien. Removal of Giardia and Cryptosporidium in drinking water treatment: a pilot-scale study[J].
Water Research, 2003, 37(5):1111-1117.
[9] LEKKES T D. A Modified Filterability Index for Granular Bed Water Filter[J]. Filtration and separation, 1981, 18(3): 214-216.

备注/Memo

备注/Memo:
收稿日期:2013-12-13 修改稿日期:2014-07-25
项目基金:国家重大水专项(2012ZX07408001)
作者简介:张建锋(1970-),男,博士,副教授,研究方向:水处理与节水技术、水资源保护.E-mail:zhangjianfeng@xauat.edu.cn
更新日期/Last Update: 2015-10-10