[1]刘 雄,郭 旗,陈建娟,等.两级加热热泵系统工作特性研究[J].西安建筑科技大学学报:自然版,2015,47(05):717-722.[doi:DOI:10.15986/j.1006-7930.2015.05.019]
 LIU Xiong,GUO Qi,CHEN Jianjuan,et al.Study on the working features of a two-stage heating heat pump system[J].J.Xi’an Univ. of Arch. & Tech.:Natural Science Edition,2015,47(05):717-722.[doi:DOI:10.15986/j.1006-7930.2015.05.019]
点击复制

两级加热热泵系统工作特性研究()
分享到:

西安建筑科技大学学报:自然版[ISSN:1006-7930/CN:61-1295/TU]

卷:
47
期数:
2015年05期
页码:
717-722
栏目:
出版日期:
2015-10-29

文章信息/Info

Title:
Study on the working features of a two-stage heating heat pump system
文章编号:
1006-7930(2015)05-0717-06
作者:
刘 雄郭 旗陈建娟刘 洋
(西安建筑科技大学环境与市政工程学院,陕西 西安 710055)
Author(s):
LIU Xiong GUO Qi CHEN Jianjuan LIU Yang
(School of Environmental and Municipal Engineering, Xi’an Univ. of Arch. & Tech., Xi’an 710055, China)
关键词:
两级加热热泵实验性能
Keywords:
two-stage heating heat pump experiment performance
分类号:
TU831.6
DOI:
DOI:10.15986/j.1006-7930.2015.05.019
文献标志码:
A
摘要:
提出了一种两级加热热泵系统,并详细叙述了其工作原理;该热泵系统在夏季工况下工作时,能够同时生产空调冷热
水,而在冬季工况下工作时,采用两级加热的方式生产空调热水;通过建立实验台,进一步研究了冬季工况下热源换热器进
出口水温对热泵系统性能的影响,结果发现:当热源换热器进出口水温分别为10/5 ℃、12/7 ℃、14/9 ℃,且热水出口水温
在40~55 ℃之间时,在相同的热源换热器进出口水温和热水出口温度下,当热水进出口温差为10 ℃时,系统的排气温度、
排气压力、压缩机功率都要比5 ℃温差时的更低,减小的幅度分别为2.01~8.32 ℃、0.078 1~0.168 7 MPa、3.0%~10.48%;
而系统的总制热量、制热COP都要比5 ℃温差时的更高,增加的幅度分别为0.69%~12.14%、4.66%~18.45%;说明所研究的
两级加热热泵系统在大的热水进出口温差下工作时,不仅性能更好,而且也更稳定.
Abstract:
This paper put forward a two-stage heating heat pump system and described its working principle in detail. In the summer,
the system can produce hot and cold water for heating and cooling simultaneously. The system can also produce hot water for heating
in winter. An experiment station was established for further studying the effects of the inlet and outlet water of the heat exchanger in
heat source side on the performance of the heat pump system in winter. The results indicated that: when the temperature of the inlet
and outlet water of the heat exchanger in heat source side are respectively 10/5 ℃, 12/7 ℃ and 14/9 ℃, and the temperature of the
outlet hot water of the hot heater is between 40 ℃ to 55 ℃, under the conditions of the same temperature of the inlet and outlet water
of the heat exchanger and the same temperature of the outlet hot water of the hot heater, the exhaust temperature and pressure of the
system and the compressor power with the temperature difference of hot water 10 ℃ are lower than these with the temperature difference
of hot water 5 ℃. And the rates decrease respectively 2.01~8.32 ℃,0.078 1~0.168 7 MPa and 3.0%~10.48%. At the same
time, the total heating capacity and heating COP of the system with the temperature difference of hot water 10 ℃ are higher than
those with the temperature difference of hot water 5 ℃. And the rates increase respectively 0.69%~12.14% and 4.66%~
18.45%.These results showed that the two-stage heating heat pump system working in the condition of big temperature difference of
hot water has better and steadier performance.

参考文献/References:

参考文献 References
[1] 张永宁. 基于案例的美国公共建筑能耗调查分析与用
能问题研究[D]. 北京: 清华大学, 2008.
ZHANG Yongning. The research and analysis of energy
consumption based on cases of public buildings in America[
D]. Beijing: Tsinghua University, 2008.
[2] 王伟, 马最良. 空调冷凝热回收热水供应系统方案研
究[J]. 哈尔滨工业大学学报, 2004, 36(11): 1531-1533.
WANG Wei, MA Zuiliang. The study of air-conditioning
heat recovery hot water supply system[J]. Journal of Harbin
Institute of Technology, 2004, 36(11): 1531-1533.
[3] 江辉民, 王洋, 马最良, 姚杨. 家用空调冷凝热回收热
水供应系统的实验分析[J]. 流体机械, 2006, 34(2):
64-67.
JIANG Huimin, WANG Yang, MA Zuiliang, YAO
Yang. Experimental analysis on domestic
air-conditioning condense heat recovery hot water supply
system[J]. Fluid Machinery, 2006, 34(2): 64-67.
[4] JIANG Huimin, JIANG Yiqiang, WANG Yang, et al. An
experimental study on a modified air conditioner with a
domestic hot water supply(ACDHWS)[J]. Energy,
2006(31): 1789-1803.
[5] 李舒宏, 武文斌, 张小松. 多功能热泵空调热水器的实
验研究[J]. 流体机械, 2005, 33(9): 48-50.
LI Suhong, WU Wenbin, ZHANG Xiaosong. Experimental
investigation on the multi-functional heat pump
Air conditioner water heater[J]. Fluid Machinery, 2005,
33(9): 48-50.
[6] JI Jie. Performance of multi-functional domestic
heat-pump system[J]. Applied Energy, 2005, 80:
307-326.
[7] 陈则韶. 冷暖空调热水三用机的功能控制[J]. 流体机
械, 2009, 37(3): 69-72.
CHEN Zeshao. Control technology of heat pump with
three functions[J]. Fluid Machinery, 2009, 37(3): 69-72.
[8] 江辉民. 带热水供应的热泵空调器的运行特性研究
[D]. 哈尔滨: 哈尔滨工业大学, 2006.
JIANG Huimin. Experimental research on the operational
characteristics of saving-energy air-conditioner with domestic
hot water supply[D]. Harbin: Harbin Institute of
Technology, 2006.
[9] GONG Guangcai. A new heat recovery technique for
air-conditioning/heat-pump system[J]. Applied Thermal
Engineering, 2008(28): 2360-2370.
[10] 樊高定, 江斌, 陈则韶, 等. 一种直热式冷暖空调热水
三用机的研究[J]. 流体机械, 2007, 35(7): 47-51.
FAN Gaoding, JIANG Bin, CHEN Zeshao. Research on
instantaneous cooling-heating-hot water multi-purpose
equipment[J]. Fluid Machinery, 2007, 35(7): 47-51.
[11] MAZZEI P, MINICHIELLO F, PALMA D. Desiccant
HVAC systems for commercial buildings[J]. Applied
Thermal Engineering, 2002, 22(5): 545-560.
[12] 白雪莲, 吴静怡, 王如竹. 基于热回收的游泳池热泵除
湿供暖系统[J]. 太阳能学报, 2004, 24(6): 838-844.
BAI Xuelian, WU Jingyi, WANG Ruzhu. Heating system
of swimming pool heat pump based on heat recovery[J].
Journal of solar energy, 2004, 24(6): 838-844.
[13] 梁才航. 热泵除湿系统的数值模拟及实验研究[J]. 工
程热物理学报, 2010, 31(11): 1813-1816.
LIANG Caihang. Numerical and experimental investigation
on heat pump dehumidification system[J]. Journal of
engineering thermophysics, 2010, 31(11): 1813-1816.
[14] 苏宇贵. 调温除湿型水环热泵机组: 中国,
200910040969.0[P]. 2009-12-16.
SU Yugui. Thermostat Dehumidifier type water loop heat
pump unit: China, 200910040969.0[P]. 2009-12-16.
[15] 余延顺, 钱普华, 张少凡. 一种双蒸发器调温除湿空调
机组: 中国, 200910183355. 8[P]. 2010-03-10.
YU Yanshun, QIAN Puhua, ZHANG Shaofan. A double
evaporator thermostat dehumidifier air conditioning unit:
China, 200910183355. 8[P]. 2010-03-10.
[16] LIU Xiaoyu, LAU Siu-Kit, LI Haorong. Optimization
and analysis of a multi-functional heat pump system with
air source and gray water source in heating mode[J]. Energy
and Building, 2014, 69: 1-13.
[17] BYRNE P, MIRIEL J, LENAT Y. Experimental study of
an air-source heat pump for simultaneous heating and
cooling—Part1: Basic concepts and performance verification[
J]. Applied Energy, 2011, 88: 1841-1847.
[18] JIANG M L, WU J Y, WANG R Z. Research on refrigerant
flow characteristics and performance of a multi-
functional heat pump system[J]. Energy Conversion
and Management, 2011, 52: 2323-2328.
[19] BAXTER V D. Comparison of field performance of a
high efficiency heat pump with and without a
desuperheater water heater[C]. ASHRAE Trans, 1983,
89(2): 180-189.
[20] 刘雄. 空调制冷设备: 中国, 201410414401.1[P].
2014-08-16.
LIU Xiong. Air conditioning refrigeration equipment:
China, 201410414401.1[P]. 2012-07-11.
[21] 刘雄. 空气处理设备水系统: 中国, 201210362440.2[P].
2012-09-17.
LIU Xiong. Water system of air handling equipment:
China, 201210362440.2[P]. 2012-09-17.
[22] STUIJ B. Waste heat recovery heat pumps for buildings:
an international overview[J]. IEA Heat Pump Central
Newsletter, 1994, 12(9): 12-19.
[23] CANE R L D, CLEMES S B, FORGAS DA. Heat recovery
heat pump operating experience[C]. ASHRAE Trans,
1994, 100(2): 165-172.

相似文献/References:

[1]刘 雄,刘 珂,姜乔乔,等.同时供冷供热的CO2双级压缩热泵循环性能研究[J].西安建筑科技大学学报:自然版,2012,44(01):126.[doi:10.15986/j.1006-7930.2012.01.021]
 LIU Xiong,LIU Ke,JIANG Qiao-qiao,et al.The performance analysis of CO2 two-stage compression heat pump cycle with simultaneously heating and cooling[J].J.Xi’an Univ. of Arch. & Tech.:Natural Science Edition,2012,44(05):126.[doi:10.15986/j.1006-7930.2012.01.021]

备注/Memo

备注/Memo:
收稿日期:2014-11-21 修改稿日期:2015-10-07
基金项目:国家自然科学基金项目(51408457)
作者简介:刘雄(1963-),男,工学硕士,副教授,主要从事制冷与热泵系统研究.E-mail: liuxiong630910@163.com
更新日期/Last Update: 2015-12-14