[1]袁 俊,于皓琳,管顺清,等.玻璃钢套筒基础切向冻胀力消减作用试验研究[J].西安建筑科技大学学报:自然版,2016,48(02):202-206.[doi:10.15986/j.1006-7930.2016.02. 009]
 YUAN Jun,YU Haolin,GUAN Shunqing,et al.Study on reduction of tangential frost-heave force on foundation with fiberglass sleeve[J].J.Xi’an Univ. of Arch. & Tech.:Natural Science Edition,2016,48(02):202-206.[doi:10.15986/j.1006-7930.2016.02. 009]
点击复制

玻璃钢套筒基础切向冻胀力消减作用试验研究
()
分享到:

西安建筑科技大学学报:自然版[ISSN:1006-7930/CN:61-1295/TU]

卷:
48
期数:
2016年02期
页码:
202-206
栏目:
出版日期:
2016-04-28

文章信息/Info

Title:
Study on reduction of tangential frost-heave force on foundation with fiberglass sleeve
文章编号:
1006-7930(2016)02-0202-05
作者:
袁 俊12于皓琳3管顺清2王学明2严福章4
1.中国科学院寒区旱区环境与工程研究所冻土工程国家重点实验室,甘肃 兰州 730000;2.中国电力工程顾问集团西北电力设计院有限公司,陕西 西安 710075;3.哈尔滨工业大学土木工程学院, 结构工程灾变与控制教育部重点实验室,黑龙江 哈尔滨 150090;4.国网北京经济技术研究院, 北京 102209
Author(s):
YUAN Jun12YU Haolin3GUAN Shunqing2WANG Xueming2YAN Fuzhang4
1.State Key Laboratory of Frozen Soil Engineering, Cold and Arid Regions Environmental and Engineering Research Institute, Chinese Academy of Sciences, Lanzhou 730000,China; 2.Northwest Electric Power Design Institute Co., Ltd. of China Power Engineering Consulting Group, Xi´an 710075, China; 3.Key Lab of Structures Dynamic Behavior and Control of the Ministry of Education, School of Civil Engineering, Harbin Institute of Technology, Harbin 150090, China; 4.State Power Economic Research Institute, Beijing 102209, China
关键词:
冻土玻璃钢基础工程单位切向冻胀力消减系数
Keywords:
frozen soil fiberglass foundation engineering unit tangential frost-heave forces reduction coefficient
分类号:
TU445
DOI:
10.15986/j.1006-7930.2016.02. 009
文献标志码:
A
摘要:
通过1:10 比例的直柱基础模型试验,对比测定了不同地温和不同含水率的粉质黏土中普通基础与玻璃钢套筒基础的单位切向冻胀力,研究了玻璃钢套筒在不同粉质黏土地质环境中对切向冻胀力的消减作用效率.研究结果表明,采用玻璃钢套筒后对冻土地基冻拔作用有明显的削弱,玻璃钢套筒切向冻胀力消减系数为0.70~0.83,切向冻胀力消减效率为17.24%~29.70%.土体含水率为20%、25%、30%时,切向冻胀力消减系数平均值分别为0.73、0.74、0.79,切向冻胀力消减效率平均值分别为27.03%、25.60%、20.51%.
Abstract:
Model tests on column foundation were conducted with a scale of 1:10 to determine the unit tangential frost-heave force of column foundation with fiberglass sleeve at different ground temperature and water contentin frozen silty clay. The reduction effect caused by fiberglass sleeve on tangential frost-heave force under different frozen geological conditions were studied as well. Results indicate that the reduction coefficient of tangential frost-heave ranges from 0.70 to 0.83 compared to column foundation without fiberglass sleeve, and the relative reduction efficiency focuse on 17.24% ~ 29.70% depending on the geological conditions.Concretely,reduction coefficients are 0.73, 0.74 and 0.79, respectively, with the water contents of 27.03%, 25.06% and 20.51%.

参考文献/References:

[1] LYAZGIN A L,LYASHENKO V S, OSTRO BOROD OVSV, et al. Experience in the prevention of frost

heave of pile foundations of transmission towers under northern conditions[J]. Power Technology and Engineering, 2004, 38(2):124-126.

[2] LYAZGIN A L. The problem of power transmission lines damage at the North of Tyumen province and the means of its decision[C]//The second conference of geocryologists of Russia. Moscow: 2001, 6-8.

[3] 刘厚健, 程东幸,余祁浩,等. 高海拔输电线路的冻土工程问题及对策研究[J]. 工程勘察, 2000,9(4):32-36.

LIU Houjian, CHENG Dongxing, YU Qihao,et al. Study on permafrost engineering problems and

engineering countermeasure of transmission line[J].Journal of Geotechnical Investigation & Surveying, 2000, 9 (4) :32-36.

[4] 童长江, 王雅卿, 刘景寿. 涂料法防冻胀的效果[C]//青藏冻土研究论文集, 中国科学院兰州冰川冻土研究所.北京:科学出版社, 1983, 139-142.

TONG Changjiang, WANG Yaqing, LIU Jingshou. Coating effect of antifrost heave[C] // The proceedings of

Tibet permafrost research, Lanzhou Institute of Glaciology and Cryopedology, Chinese Academy of Sciences, Beijing: Science Press, 1983, 139-142.

[5] LINELL KA, LOBACZEF. Design and construction of foundations in areas of deep seasonal frost and permafrost[R]. U.S.Army Cold Regions Research and Engineering Laboratory Special Report, 1980.80-134.

[6] 铁道科学院金化所, 天津师范学院化学系. 表面活性剂在铁路路基化学防冻胀中的应用研究. 铁道科学技术工务工程分册(第四册)[R]. 铁道部科学技术情报研究所, 1978.

China Academy of Railway Sciences, Tianjin normal university. Application of surfactants to antifrost heave in the railway roadbed. Railway science and technology of engineering and maintenance(Volume 4)[R]. Institute of Scientific and Technical Information of the Ministry of Railways, 1978.

[7] BIGGAR KW, SEGOD. C. Field pile load tests in saline permafrost.I. Test procedures and results[J].Canadian Geotechnical Journal, 1993, 30(1): 34-45.

[8] А.М. Пчелинцев. Физико-химические Спосоъы изменения сил примерзания грунта к фундаментам [C]//2d International Conference on Permafrost, Yakutsk, Siberia:National Academy of Sciences,1973:688-692.

[9] PENNER E, GOLD L W. Transfer of heavy forces by adfreezing to columns and foundationwalls in frost-susceptible soils[J], Canadian Geotechnical Journal, 1971,8(4): 514-526.

[10] KINOSHITA S, ONO T. Heaving force of frozen ground. I. mainly on the results of field researches: low temperature science laboratory [J].TeronKagakaSerial A, 1963(21):117-139.

相似文献/References:

[1]解北京,刘天乐,栾铮,等.冻结黏土单轴动态力学特性及本构模型研究[J].西安建筑科技大学学报:自然版,2024,56(02):183.[doi:10.15986/j.1006-7930.2024.02.004]
 XIE Beijing,LIU Tianle,LUAN Zheng,et al.Study on uniaxial dynamic mechanical properties and constitutive model of frozen clay[J].J.Xi’an Univ. of Arch. & Tech.:Natural Science Edition,2024,56(02):183.[doi:10.15986/j.1006-7930.2024.02.004]

备注/Memo

备注/Memo:
收稿日期:2015-07-28 修改稿日期:2016-04-07
基金项目:冻土工程国家重点实验室基金(SKLFSE201312),国家电网公司科技部计划项目(HQ-2013-S-EX-018),西北电力设计院科技项目(XB1-TM04-2013).
作者简介:袁俊(1983?),男,高级工程师,博士,主要从事输电线路杆塔与基础研究. Email: j.yuan@hotmail.com