[1]尹海国,李安桂.竖直壁面贴附式送风模式气流组织特性研究[J].西安建筑科技大学学报:自然版,2015,47(06):879-884.[doi:10.15986/j.1006-7930.2015.06.022]
 YIN Haiguo,LI Angui.Study on airflow characteristics of attached air curtain ventilation model[J].J.Xi’an Univ. of Arch. & Tech.:Natural Science Edition,2015,47(06):879-884.[doi:10.15986/j.1006-7930.2015.06.022]
点击复制

竖直壁面贴附式送风模式气流组织特性研究()
分享到:

西安建筑科技大学学报:自然版[ISSN:1006-7930/CN:61-1295/TU]

卷:
47
期数:
2015年06期
页码:
879-884
栏目:
出版日期:
2016-01-15

文章信息/Info

Title:
Study on airflow characteristics of attached air curtain ventilation model
文章编号:
1006-7930(2015)06-0879-06
作者:
尹海国李安桂
(西安建筑科技大学环境与市政工程学院,陕西 西安 710055)
Author(s):
YIN Haiguo LI Angui
(School of Environment and Municipal Engineering, Xian Univ. of Arch. & Tech., Xian 710055, China)
关键词:
通风气流组织竖直壁面贴附全尺寸实验流动特性
Keywords:
ventilation air distribution attached air curtain full scale experimental airflow characteristics
分类号:
TU834.3
DOI:
10.15986/j.1006-7930.2015.06.022
文献标志码:
A
摘要:
在对现有通风空调系统常用气流组织形式对比分析的基础上,提出了一种新型的竖直壁面贴附式送风模式.通过全尺寸实验测试的方法,研究了不同送风速度下竖直向贴附区和水平向空气湖区的三维速度场特性,得到了用于该模式定量研究的轴线速度衰减、送风主体厚度扩展等气流组织特性参数的计算式,为实际工程设计应用奠定了基础.研究表明,竖直壁面贴附式送风在工作区能够形成类似于置换通风的气流组织分布,同时采用条缝风口送风时具有二维特性,研究范围内偏转段的存在不会对气流组织产生影响,该模式可以近似按冲击射流理论进一步拓展研究.
Abstract:
Comprehensive utilization of the advantages of traditionally distinct airflow patterns using in HVAC system, a novel ventilation mode based on attached air curtain is presented in this manuscript. Full scale experimental is used to study the three-dimensional velocity field distribution of this mode in vertical wall-attached and horizontal floor-attached zone. The expressions of maximum velocity decay and main body thickness extension are obtained. The current studies show that the attached air curtain ventilation model can form the similar air distribution as displacement ventilation system in occupied zone. It has two-dimensional performance with using slot outlet. Meanwhile, the existed deflecting region has little influence on airflow characteristics of this ventilation model, and it can be treated as impinging jet in the further study

参考文献/References:

References

[1] ASHRAE. 2001 ASHRAE Handbook: Fundamentals[M]. Atlanta: American Society of Heating, Refrigeration and Air-Conditioning Engineers, Inc., 2001: 26.2-26.3.

[2] 马仁民. 置换通风的通风效率及其微热环境评价[J].暖通空调, 1997, 27(4): 1-6.

MA Renmin. Displacement ventilation effectiveness and evaluation of the micro thermal environment[J]. Heating Ventilating & Air Conditioning, 1997, 27(4): 1-6.

[3] 李强民. 置换通风原理、设计及应用[J]. 暖通空调,2000, 30(5): 41-46.

LI Qiangmin. Displacement ventilation: principles, design and applications[J]. Heating Ventilating & Air Conditioning, 2000, 30(5): 41-46.

[4] HAMILTON S, ROTH K W, BRODRICK J. Displacement ventilation[J]. ASHRAE Journal, 2004, 46(9): 56-58.

[5] KARIMIPANAH T, SANDBERG M, AWBI H B. A comparative study of different air distribution systems in a classroom[C]//Proceedings of the ROOMVENT 2000, Reading, UK, 2000, Vol. II: 1013-1018.

[6] MELIKOV A K, RADIM C, MILAN M. Personalized ventilation: evaluation of different air terminal devices[J]. Energy and Building, 2002, 34(8): 829-836.

[7] 林章, 周天泰, 曾志宽. 层式通风—高温空调下的出路[J]. 化工学报, 2008, 59(S2): 235-241.

LIN Zhang, CHOW T T, TSANG C. Ventilation system for higher room temperature setting[J]. Journal of Chemical Industry and Engineering, 2008, 59(S2): 235-241.

[8] CAO G Y, SIR?N K, KILPEL?INEN S. Modeling and experimental study of performance of the protected occupied zone ventilation[J]. Energy and Building, 2014, 68(Part A): 515-531.

[9] 李安桂, 邱少辉, 王国栋. 竖壁贴附射流空气湖模式通风系统:中国, 200810017349.0 [P]. 2008-01-21.

LI Angui, QIU Shaohui, WANG Guodong. A downward directed vertical wall jet ventilation system based on air lake model: China, 200810017349.0 [P]. 2008-01-21.

[10] LI Angui, YIN Haiguo, ZHANG Wangda. A novel air distribution method-Principles of air curtain ventilation[J]. International Journal of Ventilation, 2012,10(4): 383-390.

[11] 李安桂, 尹海国, 陶鹏飞. 一种出风均匀且风口可调式静压箱[P]. 中国, 201010549210.8, 2012.07.25.

LI Angui, YIN Haiguo TAO Pengfei. A plenum chamber with uniform air supply and adjustable air outlet[P]. P.R. China, 201010549210.8, 2012.07.25.

[12] THORSHAUGE J. Air-velocity fluctuations in the occupied zone of ventilated spaces[J], ASHRAE Transactions, 1982, 88(2): 753-764.

[13] RAJARATNAM N. Turbulent Jets[M]. Amsterdam: Elsevier, 1976: 211-213.

[14] ASHRAE. 1993 ASHRAE Handbook: Fundamentals[M]. Atlanta: American Society of Heating, Refrigeration and Air-Conditioning Engineers, Inc., 1993.

[15] CHO Y J, AWBI H B, KARIMIPANAH T. Theoretical and experimental investigation of wall confluent jets ventilation and comparison with wall displacement ventilation[ J]. Building and Environment, 2008, 43(6): 1091-1100.

[16] KARIMIPANAH T, AWBI H B. Theoretical and experimental investigation of impinging jet ventilation and comparison with wall displacement ventilation[J]. Building and Environment, 2002, 37(12): 1329-1342.

[17] CAO G. Modelling the attached plane jet in a room[D]. PhD thesis, Finland: Helsinki University of Technology, 2009.

[18] F?RTHMANN E. Turbulent jet expansion[R]. Washington, D.C.: National Aeronautics and Space Administration, 1934: No. TM-789.

[19] VERHOFF A. The two-dimensional turbulent wall jet without an external free stream[R]. Princeton: Princeton University, 1963: No. 626.

[20] SCHWARZ W H, COSART W P. The two-dimensional turbulent wall jet[J]. Journal of Fluid Mechanics, 1961, 10(4): 481-495.

[21] BELTAOS S, RAJARATNAM N. Plane turbulent impinging jets[J]. Journal of Hydraulic Research, 1973, 11(1): 29-59.

相似文献/References:

[1]狄育慧,王善聪.利用Airpak模拟室内气流组织的误差分析[J].西安建筑科技大学学报:自然版,2013,45(01):73.[doi:10.15986/j.1006-7930.2013.01.011]
 DI Yu-hui,WANG Shan-cong.Error analysis of simulation of indoor airflow organizations with Airpak[J].J.Xi’an Univ. of Arch. & Tech.:Natural Science Edition,2013,45(06):73.[doi:10.15986/j.1006-7930.2013.01.011]
[2]狄育慧,徐子龙,邓保顺.火车站候车厅不同回风形式的热环境研究[J].西安建筑科技大学学报:自然版,2014,46(05):742.[doi:10.15986/j.1006-7930.2004.05.022]
 DI YuhuiXU ZilongDENG Baoshun.Study on different forms of return air indoor thermal environment in the large space of Xi’an Railway Station[J].J.Xi’an Univ. of Arch. & Tech.:Natural Science Edition,2014,46(06):742.[doi:10.15986/j.1006-7930.2004.05.022]
[3]李安桂,陈 强,尹海国,等.十三陵电站坝体廊道通风动态换热节能设计理论基础研究[J].西安建筑科技大学学报:自然版,2015,47(06):874.[doi:10.15986/j.1006-7930.2015.06.021]
 LI AnguiCHEN QiangYIN HaiguoGAO Ran.Study on dynamic heat transfer and basic theory of energy saving design of Shisanling Hydropower Station based on the dam tunnel ventilation[J].J.Xi’an Univ. of Arch. & Tech.:Natural Science Edition,2015,47(06):874.[doi:10.15986/j.1006-7930.2015.06.021]
[4]李安桂,李明明.小微空间通风空调贴附式气流组织的有效性研究[J].西安建筑科技大学学报:自然版,2016,48(01):115.[doi:10.15986/j.1006-7930.2016.01.019]
 LI Angui,LI Mingming.Research on the effectiveness of air curtain ventilation air distribution for small micro–space[J].J.Xi’an Univ. of Arch. & Tech.:Natural Science Edition,2016,48(06):115.[doi:10.15986/j.1006-7930.2016.01.019]
[5]李安桂,刘旺兴,要聪聪,等.竖壁贴附射流加导流板呼吸区送风气流组织CFD及试验研究[J].西安建筑科技大学学报:自然版,2016,48(05):738.[doi:10.15986/j.1006-7930.2016.05.020]
 LI Angui,LIU Wangxing,YAO Congcong,et al.CFD and the experimental study of air distribution in the breathing zone based on air curtain ventilation with deflector[J].J.Xi’an Univ. of Arch. & Tech.:Natural Science Edition,2016,48(06):738.[doi:10.15986/j.1006-7930.2016.05.020]
[6]黄 翔,李婷婷,刘凯磊,等.乌鲁木齐某数据中心热环境分析及气流组织优化研究[J].西安建筑科技大学学报:自然版,2019,51(01):104.[doi:10.15986/j.1006-7930.2019.01.016]
 LI Tingting,HUANG Xian,LIU Kailei,et al.Thermal environment analysis and air distribution optimization for a Data Room in Urumqi[J].J.Xi’an Univ. of Arch. & Tech.:Natural Science Edition,2019,51(06):104.[doi:10.15986/j.1006-7930.2019.01.016]
[7]尹海国,李安桂,刘志永,等.方型柱面贴附置换通风模式影响因素分析[J].西安建筑科技大学学报:自然版,2016,48(04):591.[doi:10.15986/j.1006-7930.2016.04. 022]
 YIN Haiguo,LI Angui,LIU Zhiyong,et al.Analysis on influence factors of square column attached displacementventilation mode[J].J.Xi’an Univ. of Arch. & Tech.:Natural Science Edition,2016,48(06):591.[doi:10.15986/j.1006-7930.2016.04. 022]

备注/Memo

备注/Memo:
收稿日期:2015-01-27 修改稿日期:2015-12-21
基金项目:国家自然科学基金资助项目(51408477,50778145);陕西省自然科学基础研究计划项目(2014JQ7235);陕西省教育厅专项科研计划项目(14JK1415);西安建筑科技大学科技项目(QN1418)
作者简介:尹海国(1987- ),男,博士,讲师,主要从事通风空调新技术、个性化送风研究.E-mail: yinhaiguo@xauat.edu.cn
更新日期/Last Update: 2016-01-29